Summary
Type: SPE
Application #: 302220
Catalog#: 730075 - SPE Cartridges, Chromabond, Silica, 6ml, PP, 1000mg, 30/pk
Detection: Qualitative and quantitative determination of the extracted compounds using HPLC/UV and HPLC/MS. First 2 ml were collected in sample vials of 3,74 ml volume and filtered by iso-disc syringe-tip filter
Conditions: Column conditioning: with 2 cm3 n-pentane at atmospheric pressure
Sample application: The 20 ml sample passed through the cartridge under vacuum at a flow rate of 2,5 ml/min.
Column washing: wit
Authors: Koreh O Ludányi K Vekey K Jávorszky E Molnár E Torkos K Borossay J
Source: Rapid Communications in Mass Spectrometry 12 1515-